Description:
I have PR402 controller to which two PRT12 readers are connected: ID0 and ID1. After programming function [57]: "Set Predefined T&A mode (momentary)" on F1 and F2 function keys - and assigning [T&A - Entrance] and [T&A - Exit] to each key - change of the mode is possible on both terminals but proper [Entrance] and [Exit] mode is recorded only on ID1 terminal. On ID0 terminal there is only default T&A mode event recorded. What is the cause?
Solution:
The cause of the problem is that dynamic change of T&A mode is possible on ID1 terminal only. In order to control T&A mode using function keys of ID0 terminal it is necessary to enable T&A mode multiplication from ID1 terminal. To do this enable option Term.ID0 follows T&A mode of term.ID1 in Controller properties > Options.